Loading units, dwelling units and shower diversity — B.G. Smith, Plumbing Design
Probable simultaneous flows for home units, flats, town houses and villa homes — TABLE 56. Enter the number of units and pick the column that matches the unit type.
For a main-to-meter distance not exceeding 30 m. At 30 or more dwelling units the pressure loss due to flow must be calculated and these sizes adjusted.
Count the fixtures. Each carries the loading units from TABLE 47; the total is read against TABLE 48 to give the probable simultaneous flow.
Split the run into sections and count the fixtures added in each section. Each section is then read against TABLE 48 at the loading units it actually carries — its own plus everything downstream of it — which is why the section nearest the incoming end is the largest. Click the diagram to add or remove a section.
The same sections, but you type the flow instead of counting fixtures. By default each section carries exactly the flow you enter; tick auto on a section to have it total everything downstream instead.
Showers are a full-flow fixture: TABLE 47's note says rows of showers in ablution blocks must not be diversified. Each shower's demand is added at 100%.
Takes the sections and flows from either sectional tab. Friction is Hazen–Williams at the nominal pipe size, matching the practice spreadsheet; the k factors, the meter loss and the system-head layout are the spreadsheet’s own. Lengths, sizes and fitting counts are entered here.
Choosing Fire sprinkler / drencher switches the whole tab to AS 2118.1 Cl 14.10: the standard’s own Hazen–Williams form (P = 6.05×107·Q1.85/(C1.85·d4.87), Q in L/min, d the mean internal diameter), its Table 14.10(A) C values, its Tables 14.10(B)/(C) internal diameters for steel to AS 1074 and copper to AS 1432, and fittings converted to equivalent pipe length from Table 14.11.1 — which is tabulated for C = 120 only, so it is scaled for other C values as that table directs. AS 2118.2 carries no hydraulics of its own and cross-refers to AS 2118.1, so the one basis covers drencher systems too. Cl 14.12 asks junctions to balance to ±2 L/min and ±0.5 kPa; Cl 14.15 makes velocity pressure optional, and these clauses set no velocity limit — a single most-remote-path estimate, not a balanced loop analysis.
The single lookup behind every other tab — TABLE 48's flow read against the practice's size table. Sizes are rounded up to the next available size.
The reverse lookup — what the table allows for a given flow.