Stormwater Pipe Sizing

Enter a flow or an area, and each segment's own grade — get the pipe size

Click to
join
Line
no.
Segment Grade
%
Input This segment (L/s) Running total (L/s) Pipe size Velocity (m/s)

Sizing method: Manning's equation, n = 0.009, with the nominal DN taken as the bore and the pipe running full — the method used in the office spreadsheet. Taking the nominal as the bore deliberately understates capacity, so the sizes are conservative against the real bores (DN 100 is actually 104 mm, DN 150 is 153.6 mm) and against the Colebrook–White method of AS/NZS 3500.3 Cl 5.4.11.2, which is what governs a pipe drain. Table 5.4.9 gives PVC roughness as n = 0.009 to 0.010; 0.009 is the value carried here.

The chosen size is the smallest that carries the running total at the grade entered, and never below DN 100. Available sizes: DN 100, 150, 225, 300, 375, 450. Velocity is taken at the running total; Cl 5.4.11.2(d) limits the full-pipe velocity to 2.0 m/s and the note to that clause recommends 1.5 m/s for a pit outlet pipe.

Manning — quick pipe capacity

Use this to pick a pipe size for a known flow, or to find what a known pipe will carry. The pipe is assumed to run full, which is the usual design case for a stormwater drain.

Flow → size: enter the design flow in litres per second.
Size → flow: pick a pipe and read its maximum flow.
Grade: the fall, as a percentage — 1 means 1% (1 in 100), the common minimum.
Material: sets the Manning roughness n. Custom lets you type your own.

DNBore (mm)Area (m²) Capacity (L/s)V at capacity (m/s)

Working

Q = (1/n) · A · R2/3 · S1/2, pipe running full, A = πD²/4, R = D/4, S = grade/100. Capacity scales with S1/2, so doubling the grade raises it by about 41%.

Manning — partially full circular pipe

For a pipe running part full — a drain at low flow, or a pipe sized with spare capacity. The geometry is exact: the wetted area, perimeter and hydraulic radius all follow the depth, so this is the true result rather than a full-bore approximation.

Depth of flow is how deep the water sits inside the pipe, measured from the invert. It runs from 0 up to the pipe diameter and no further — at the diameter the pipe is running full. A depth greater than the pipe cannot occur, and this form will say so rather than guess.
Depth → flow: enter a depth, read the discharge.
Flow → depth: enter a discharge, and the depth needed is solved.

Working

Q = (1/n) · A · R2/3 · S1/2 with the partly-full A, P and R.
Less than half full: h = y, θ = 2·acos((r−h)/r), A = (r²/2)(θ−sinθ), P = rθ.
More than half full: h = 2r−y, θ = 2·acos((r−h)/r), the upper segment is subtracted from the full circle, so A = πr² − (r²/2)(θ−sinθ) and P = 2πr − rθ.
Geometry after H. Bengtson, Partially Full Pipe Flow Calculations. Its two worked examples reproduce here to better than 0.3% — the small gap is that the imperial workbook uses 1.49 as the Manning constant where the exact conversion to SI is 1.4859, and this tab is strictly SI.

Manning — channels and other shapes

Open channels and box sections — a V-drain, a rectangular swale or kerb channel, a trapezoidal drain, or an RHS box. Depth is the water depth in the channel, measured up from the invert, and it cannot exceed the depth of the section.

Grade: the fall as a percentage — 1 means 1% (1 in 100).
Material: sets the Manning roughness n; Custom lets you type your own.

Working

Q = (1/n) · A · R2/3 · S1/2, S = grade/100, A and P from the shape.
Rectangular: A = b·y, P = b + 2y.
Triangular (V): b is the width at the top of the water, A = b·y/2, P = 2·√((b/2)² + y²).
Trapezoidal (base b, side slope 1 in z): A = b·y + z·y², P = b + 2y·√(1+z²).
Froude number Fr = V/√(g·D) with D = A/T the hydraulic depth and T the surface width; Fr < 1 is subcritical, Fr > 1 supercritical.
Depth × velocity is the usual pedestrian-safety check for an overland flow path — the common limit is 0.4 m²/s.
Roughness values: the pipe list follows the practice workbook; the channel entries are AS/NZS 3500.3:2018 Table 5.4.9.

Hydraulic grade line — energy profile

Draws the hydraulic grade line along a stormwater line and shows where it sits against the ground and the pipe. Enter each pipe run as a row, working from the upstream end down to the outfall — row 1 is the head of the line, the last row discharges at the outfall.

U/S and D/S GL are ground levels at the ends of the run (m AHD). U/S and D/S IL are the pipe invert levels at the same ends. K is the pit loss coefficient at the upstream end — the head lost passing through the access structure, as a multiple of the velocity head.
The line is worked backwards from the outfall: start from the water level there and add friction and pit losses going upstream, which is the standard energy method and the way the check sheet does it.

Section L
m
Q
L/s
D
mm
n K
pit
U/S GL
m
D/S GL
m
U/S IL
m
D/S IL
m

Hydraulic grade line

Ground Pipe HGL Freeboard limit

Working

Section results

Friction loss uses the full-pipe Manning slope Sf = v²n² / R4/3, with R = D/4 for a circular pipe running full — the same form as the practice sheet, and equal to Q²n²/(A²R4/3) with the SI constant of 1.
Pit loss hm = K · v²/2g. K is either the coefficient you enter, or solved from the access structure itself — choose From pit in the K column and give the structure's diameter, the deflection angle between the incoming and outgoing pipes, and the bench type. The manual (ODOT 13-G, Eq 8–13) builds K = Ko·CD·Cd·CQ·Cp·CB; CQ and Cp sit at 1 unless three or more pipes enter at like elevation or another inflow plunges in, which this run-by-run model does not represent. daho is the depth in the structure, which is the HGL you are solving for, so the two are solved together.
Energy equation HGLus = HGLds + hf + hm. Each pipe is treated as uniform, so the velocity head is the same at both ends and cancels — this is Eq 6-22 of the manual with equal velocity heads, and matches the sheet.
Critical depth is where Q²T/(gA³) = 1, and is shown at every pit. TxDOT Section 3 step 5 sets the starting HGL for the next run to the higher of critical depth and the calculated HGL; the tick box applies that floor. It is off by default so the figures match the practice sheet exactly.
Flooding check: the HGL at a pit must stay below the ground level less the freeboard. Cover check: ground level less the pipe obvert must be at least the minimum cover.

Stormwater Pipe Sizing — design summary

Manning's equation, n = 0.009, nominal DN taken as the bore, pipe running full

Project / reference: —
Date: —
Grade: —
Minimum pipe: DN 100
NodeSegmentGrade This segment (L/s)From line Running total (L/s)Pipe sizeVelocity (m/s)
Total flow at the outfall—

Sizes from Manning's equation with n = 0.009, the nominal DN taken as the bore, pipe running full — the office spreadsheet method. Using the nominal as the bore understates capacity, so these sizes are conservative against the true bores and against AS/NZS 3500.3 Cl 5.4.11.2 (Colebrook–White, k = 0.015 mm for plastics). Minimum size DN 100. Velocity is taken at the running total; Cl 5.4.11.2(d) limits the full-pipe velocity to 2.0 m/s and the note to that clause recommends 1.5 m/s for a pit outlet pipe.

Prepared / checked by
Date