Design flows, diameter range, velocity, detention, pump cycling and pressure class — WSA 04 Sewage Pumping Station Code, Part 1 Section 10 and Appendix D
Appendix D works from the design flows rather than from a chosen pipe. Enter the flows and the length to the high point and the calculator returns the range of internal diameters that satisfies every WSA 04 constraint; then trial a size against the pumping rate you intend to run. Everything downstream — velocity, detention, starts, head, pressure class — follows from those two choices.
Pick a pipe and a pumping rate. The pumping rate must sit between Qp-min (the greater of the design wet weather flow and the slime-stripping flow) and Qp-max (the maximum velocity limit) — the calculator shows both, and tells you what the trial rate does to starts, detention and velocity.
The whole catalogue against this station's flows at the trial pumping rate. Sizes outside the feasible diameter range are greyed; the governing limit for each row is named. This is the comparison that decides the size, so the head and pressure columns carry the trial rate through to the pump too. How hard each size is on the pipe itself — cycling, velocity and temperature — is on the Pipe life tab.
Bores are typical manufactured mean internal diameters — confirm against the supplier's table before ordering. WSA 04 uses the internal diameter throughout (Preface).
The Code takes the static head to the highest point on the hydraulic grade line — at the discharge, or at the highest physical point where the main undulates — and adds one internal diameter to it (Clause 10.3.2). The mean operating level is the mid-point of the wet-well working range.
Colebrook–White, solved iteratively, with the Swamee–Jain approximation shown alongside as a check (Clause 10.3.3). The absolute roughness follows the Code's velocity table — 0.6 mm at 1 m/s, 0.3 mm at 1.5 m/s, 0.15 mm at 2 m/s — interpolated for the velocity actually calculated, and the kinematic viscosity follows the sewage temperature.
Clause 10.3.4 leaves the coefficients to Miller, the Hydraulic Institute or the Australian Pump Manufacturers Technical Handbook. The values below are typical published figures for a submersible station — replace any of them with the manufacturer's number, and add rows for what this station actually has. Reductions in diameter are not permitted, so every fitting is on the main's velocity.
| Qty | Fitting or valve | k each | k total | |
|---|---|---|---|---|
| Total Σkf | — |
Head against flow for this main at the trial diameter. The pump has to intersect this curve at the pumping rate chosen on the first tab; the WSA also requires it to intersect the system curve at snort level and at overflow level (Cl 6.2). Zoom in and the labels get out of each other's way — they are placed to measure.
Maximum design pressure is the static head at the lowest pumping level, plus the friction head at the pumping rate, plus an allowance for surge of not less than 200 kPa (Clauses 10.4.1, 10.4.2). It is the pressure every pipe, fitting and anchorage is selected and tested against, and it goes on the drawings.
Three separate tests, and the pipe has to pass all of them: MAOP greater than the maximum design pressure, MAOP de-rated for the 12-month average temperature, and — for thermoplastics — MCPR greater than the maximum design pressure range. Temperature and fatigue are not additive; the worse of the two governs (Cl 10.6.5). The minimum class for any pressure main is Class 12.
Buried sewer systems “shall be designed for a nominal asset life of at least 100 years without rehabilitation” (Cl 1.6.2). Everything else in a pumping station is replaced on a shorter cycle, and those cycles are what drive the maintenance plan rather than the pipe. This tab works out what is wearing the main out on this duty and how many years each mechanism allows.
| Item | Minimum design life (years) | Note |
|---|---|---|
| Sewers, pressure mains, civil structures | 100 | The main itself — no rehabilitation within the life |
| Valves | 30 | Isolating, reflux and air valves |
| Electrical equipment | 25 | Switchgear, cabling, telemetry |
| Pumps | 25 | Replacement cycle, not a design life of the station |
| Pipework | 50 | Discharge pipework inside the chamber |
| Wet-well appurtenances | 20 | Ladders, covers, guides, level instruments |
| Instrumentation, SCADA and control | 15 | Shortest cycle on the site |
This is the mechanism the Code actually quantifies, and it is a clock rather than a check. Every pump start applies a pressure cycle of amplitude ΔP. Table 10.2 gives the fatigue de-rating factor F that a thermoplastic pipe retains at a given total number of cycles, and the pipe is acceptable only while PN/10 × F is still greater than ΔP. So the cycles accumulate until the pipe crosses its own fatigue envelope — and the year that happens is the life the duty allows.
Velocity does not consume the wall by a formula the Code gives, but it sets the two things that do: the shear stress at the wall, which carries solids and strips slime, and the scouring of internal surfaces that the 3.5 m/s cap exists to limit (Cl 10.3.6(f)(iii)). Below 0.9 m/s the main silts and slimes; above 3.5 m/s it is scoured and the power bill climbs. The sweep shows both sides of that band for this bore.
The mechanisms above, side by side. The shortest one governs what the main will actually do, and the margin is how much of that allowance this duty uses up.
Every item below is a requirement of WSA 04 Part 1 that applies to a pressure main. The tick list is saved with the project, so the drawing set can point at it. Items marked with a clause reference are normative; the calculator shows the computed value beside the ones it can check.
As printed in Appendix D and Section 10. The calculator uses dimensionally consistent forms of the same equations, with lengths in metres, flows in litres per second and detention time in hours.