Method. AS/NZS 5601.1:2022 Appendix F is built on the
Churchill friction factor equation with the fundamental isothermal flow calculation for
compressible fluids, iterated until the flow and friction factor agree (Cl F.1.4). Every flow it
produces is for a pipe of minimum internal diameter (Cl F.1.2) and includes a
fitting allowance equivalent to a 50 % extension of the length (Cl F.1.3) —
both are applied here. The length you enter is the straight developed length; the tool works on
1.5 × that length, exactly as the tables do.
1 — Inputs
2 — Result
Working a run. Enter the load added at each node (the appliance) and
the length of each section. Leave the size blank and the tool picks the smallest size whose drop
fits the allowance — the total allowable drop divided by the run length, which is the method
Cl F.3.1 uses. Type a size in any row to fix it. The residual pressure carries from one node to the
next, and the last node is checked against the pressure you say the appliance needs.
Run data
The total allowable drop is
— kPa over the run, giving
— kPa/m to size the un-fixed sections with.
Section
Load added at the node (MJ/h)
Section total (MJ/h)
Diversity factor
Length (m)
Size (blank = size it)
Result
Validation — this model against the Standard's own sizing tables
Each of these tables is natural gas, at the pressure drop and
supply pressure it is written for — the low-pressure tables at 0.12 kPa and around
1.25 kPa, and Table F.14 at 10 kPa and around 70 kPa. The model is run at each
table's own conditions. The high-pressure row is there because the gas density changes with
pressure, and a model that ignores it reads low. For the rows read out of the PDF:
Gas Pipe Sizing — design summary
AS/NZS 5601.1:2022 Appendix F — Churchill friction factor, isothermal flow,
fitting allowance of 50 % of the straight length (Cl F.1.3)
Project / reference:—
Date:—
Method:—
Gas:—
Pipe material:—
Bore basis:—
Notes
Description
Value
Unit
Basis
Result
—
—
—
Gas Pipe Sizing — whole-system schedule
AS/NZS 5601.1:2022 Appendix F — Churchill friction factor, isothermal flow,
fitting allowance per Cl F.1.3