Required flow × duration → storage volume → tank selection
Concept check — not a design. The tool only multiplies flow by
duration. The duration is not calculated here — it comes from AS 2118.1 or
AS 2419.1 for the hazard, the system type and the building, so enter the figure that applies
from the current edition. Fire service tanks are above ground, so height is the only
factor — there is no depth to enter. Always confirm the tank’s
effective capacity, not its gross.
1 — Required volume
Duration is entered, not calculated: confirm it against AS 2118.1 or
AS 2419.1 for the occupancy and system type in front of you. The margin is optional and is
added on top.
2 — Tank selection
Standard panels are up to 1000 mm wide,
so length and width are normally whole metres. Alstore builds rectangular MEGA panel fire
tanks to 5.5 m high.
Pioneer’s published volumes do not
include freeboard, so every tank below has 400 mm taken off its wall height
and the effective storage volume is listed. Models that meet the required volume
from part 1 are listed smallest first.