For Class A fire risks the travel distance from any point to the nearest extinguisher shall not be greater than 15 m, no matter what the tables say about floor area. That is the hard limit that forces a second extinguisher into a large floor plate — a single unit can only reach 15 m in every direction. The largest square a unit can stand at the centre of is 15√2 = 21.2 m a side, about 450 m² — not the 707 m² of the circle itself, because the corners of the square have to fall inside it.
Distribution follows the hazard present in the area, not the size of the area (Cl 4.1). Extinguishers of a lower rating cannot be added together to reach a higher rating, and each unit of the same type must be sited separately unless they are assembled at a fire point.
| Fire hazard | Minimum rating | Max floor area per extinguisher (m²) | Max floor area per extinguisher where a fixed suppression system is provided (m²) |
|---|
Where a Class A risk involves electrically energised equipment, the extinguisher — or another one available in the area — must have an E classification (Cl 4.2.1).
| Fire hazard | Minimum rating | Travel distance from the extinguisher to the hazard (m) | Max floor area per extinguisher (m²) |
|---|
| Risk | Requirement | Clause |
|---|---|---|
| Significant switchboard A switchboard in a required exit, not to AS 3000, an emergency services board, 3-phase, or vertically aligned serving a floor of two or more storeys. |
An extinguisher located between 2 m and 20 m from the board. A 5 kg CO2 extinguisher, or another type with a minimum classification of 1A:E fitted with a hose, and it must be the extinguisher closest to the board. | 4.4.2 |
| Office electrical and electronic risks | Maximum distance from the extinguisher's normal location to the risk is 20 m where there is a large density of equipment (computer centres, broadcast studios, telephone exchange rooms), or 40 m for a lesser distribution such as offices with computers and photocopiers. | 4.4.3 |
| Cooking oils and fats (Class F) | An extinguisher located between 2 m and 20 m from the risk, carrying an F classification rated to the surface area of the hazard, and it must be the extinguisher closest to the risk. | 4.4.4 |
| Combustible metals (Class D) | Special-purpose extinguishers only — the ratings are tested to international standards and this Standard gives no sizing rule. Seek expert advice. | Fig A1 |
| Item | Requirement |
|---|---|
| Position | Conspicuous and readily accessible, along normal paths of travel and near exits. Not where reaching it could present a hazard to the user. |
| Location sign | A sign is required above or adjacent to each extinguisher — white symbol, border and letters on a red field, R13 Signal Red to AS 2700. One sign may indicate several extinguishers in the one location. |
| Extinguisher mounting height | Top of the extinguisher not more than 1200 mm above the floor, and the base not less than 100 mm above it. Vary only where there is a risk of dislodgment, and then only if ready access is kept. |
| Sign height | Bottom of the location sign not less than 2000 mm above the floor. |
| Mass | A portable extinguisher has a gross mass not greater than 23 kg when charged to design capacity. |
| Classification | Rated to AS/NZS 1850, marked on the unit. Select for capability against the actual risk. Non-compliant or empty units are commissioned and installed to AS 1851.1. |
Enter the floor area on its own and the tool assumes a square floor plate for the 15 m travel check. Give the length and width as well and it uses the real shape — which matters, because a long thin building needs more extinguishers than its area alone suggests.
Enter a floor area above.
| Extinguisher | Band colour | A wood, paper, plastics |
B flammable liquids |
C flammable gases |
E energised electrical |
F cooking oils, fats |
D combustible metals |
|---|
A fire blanket is suitable for Class F (cooking oils and fats) and limited on every other class except gases and metals, where it must not be used. It is covered by AS 2444 alongside the extinguishers and appears in Figure A1.
| Type | Typical size | Typical marked rating | Suits |
|---|
Complete the Select & size tab first.