Peak-hour demand, first-hour delivery and recovery · AS/NZS 3500.4 heated water · Rinnai Ch 7 sizing method
Use showers or kitchen for a peak-hour volume (sizes storage), or direct flow for a simultaneous rate (sizes instantaneous). Both are reported, so either heater family can be checked.
Models are listed where they meet the demand; the smallest that does is highlighted. First hour is storage plus one hour of recovery. Instantaneous units are compared on flow capacity instead.
Loading units from the practice table (SHR 4, BSN 1, SK 3, WC 2, TUB 3, W/M 3), summed along the run and read against the flow/size table at the 1.5 m/s reference velocity — the same basis as the cold water calculator, so the two stay consistent.
The heat lost from the flow and return mains is what sets the circulating flow; the loop's resistance is what sets the pump duty. Method follows the practice's Hot Water Design Aid: heat loss per metre by size, circulating flow at 4.2 kJ/kg·K, a Darcy friction factor of 0.0234, and an allowance over the pipe friction for bends, tees and valves.