Concept check — not a design. This answers “is that roughly
big enough?” and “roughly what head will it cost?” for a rising main, a pump
discharge or any sewage pressure pipe. WSA 04 requires Darcy–Weisbach with
Colebrook–White for pressure mains (Cl 10.3.3) — that is the default here — and it
sets the velocity limits at 0.9 m/s minimum below DN 300, 1.5 m/s preferred and
3.5 m/s maximum (Cl 10.3.5). For the sizing of the main itself — diameter range,
slime stripping, detention time, pump starts and pressure class — use the
Rising Main calculator.